Setup & Commissioning (continued)

Light level

The light level feature allows lighting to

remain OFF during daylight, regardless of

occupancy. Daytime operation is at 200

footcandles (factory setting). Nighttime

operation is at .2 footcandles.

The adjusting screw turned fully clockwise

means daylight operation at approx. 200

fc (factory setting). Turning fully counter-

clockwise means nighttime operation at

.2 fc. When adjusting the detection zone

and for the performance test in daylight,

the adjusting screw must be turned fully

clockwise.

Time delay

Time delay is the period of time lights

remain on after the last detection.

Adjustment ranges from 30 sec (factory

setting) to 30 min.

The adjusting screw turned fully counter-

clockwise means the shortest time and

fully clockwise means the longest. The

time delay is restarted by any movement

detected before this time elapses. The

shortest time setting is recommended

when adjusting the detection zone and for

the performance test.

Note: Every time the light switches off, it

takes approximately two seconds for the

sensor to start detecting movement again.

Reach/sensitivity

The sensor’s reach setting can be

adjusted. Turning the adjustment screw

fully counter-clockwise selects minimum

reach (about 3.3 feet) and fully clockwise

selects maximum reach (about 26 feet).

Time delay: 30 seconds
to 30 minutes

Light level: .2 (night) to 200
(day) footcandles

Sensitivity (middle): adjusts
coverage reach from approx
3.3 feet to 26 feet

7

Coverage size

The HFLUM2-120 coverage is 360°

and its reach ranges from 3.3 to 26

feet (see next page for reach/sensitivity

adjustment). Actual coverage may vary

depending on luminaire confi guration and

environmental conditions.

Lamp seasoning

Some fl orescent lamp manufacturers

recommend seasoning or “burning in”

lamps. To meet this recommendation, the

following seasoning procedure should be

carried out for new fl uorescent lamps.

• Connect luminaire, switch ON for at

least one minute

• Switch power supply OFF/ON twice

(main or light switch within 0.5 – 1 sec)

• Alternatively, you can start the

seasoning process by using the

potentiometers. Turn all 3 setting

controls fully clockwise, then turn

the middle setting control (time) fully

counter-clockwise and fully clockwise

again (within 10 sec)

• The seasoning process is confi rmed by

switching the light OFF and back ON

again twice

• The light is now left ON for 100 hours

without sensor function. Do not

disconnect the light from the main

power supply during this period.

• The luminaire automatically returns to

sensor mode after 96 hours

3.3 - 26 ft

1 - 8 m

3.3 - 13 ft

1 - 4 m

Setup & Commissioning

6

Test mode

• Ensure that the sensor is in test mode.

- set time delay to minimum setting of

30 seconds

- set light level to maximum

(“day” setting, light level function

overridden)

- set sensitivity to minimum

• Turn power ON at the circuit breaker

(lights will turn ON). After a warm up

period of up to one minute, lights will

turn OFF if the sensor does not detect

motion.

• Walk in view of sensor, lights should turn

ON. Be still for 30 seconds and lights

should turn OFF.

After setup and commissioning tests are

complete, adjust the light level, time delay,

and reach settings to fi t the application

needs.