On low high 1 2 3 4 – STEINEL HBS 200 Manuel d'utilisation
Page 3

Time
ON
Low
High
1 2 3
4
Mounting
HBS 200 Product Overview
120/230/277
VAC
50/60Hz
PIR
Aisle
way
Product description
The HBS 200 sensor provides effective lighting
control in high bay aisle way applications. The
sensor contains two dual-element pyroelectric
detectors and is engineered to perform at a
wide range of mounting heights, up to 45 feet. It
mounts directly to a high bay lighting fi xture, or
to a junction box.
1/2 inch threaded nipple
Lock nuts
Time delay setting DIP switch
Light level trimpot
Detection lens
The HBS 200 has an aisle way coverage of up
to 100 feet when mounted at 40 ft.
1
2
3
4
5
IP20
Fixture
or J Box
Mount
• The HBS 300 and HBS 200 lens must have
a clear, unobstructed view of the detection
area.
• Sensor should be 6 to 8 feet away from
heating/cooling supply ducts.
End of fi xture mounting
Junction box mounting
Placement guidelines
• Ideal mounting height is up to 45 feet.
• Sensor must be mounted on a stable platform.
The HBS 300 and HBS 200 typically mount to
a 1/2” knockout at the end of a high/low bay
lighting fi xture. The sensor's lens should be
mounted below the bottom edge of the fi xture.
The EM 1 Extender Module is recommended
if the knockout at the end of the fi xture is
located greater than 1/2” from the bottom
edge of the fi xture.
If mounting to the end of a fi xture is not
possible, the HSB 300 and HBS 200 can
be mounted to any junction box with a 1/2”
(trade size) knockout. This may be necessary
if the fi xture location of the control area has
an obstruction that would block the view of
the sensor (for example: racking is directly
beneath the fi xture).
EM 1
Fixture
Junction
box
HBS sensor
Fixture
10
20
30
40
radial
tangential
40 ft
13 ft
50 ft
53 ft 53 ft
50 ft
1
3
4
5
2
HBS sensor
HBS sensor
4
5
Voltage
Load rating
Time delay
Light level
Coverage
Environment
Dimensions
5 year warranty
UL and CUL Listed, RoHS Compliant
120/230/277 VAC, 50/60 Hz
120 VAC: 0-800 watt ballast or Tungsten - 1/4 hp
277 VAC: 0-1200 watt ballast
15 sec to 30 min
.2 - 200 footcandles ; 2 - 2000 lux
100 x 13 ft (30.48 x 3.96 m) diameter reach
IP20 rated, -4°F to +122°F, -20°C to +50°C
3.9 x 3.9 x 2.72 in; 99 x 99 x 69.1 mm
nipple length .62 in (15.75 mm)
Specifi cations
www.steinel.net (800) 852-4343
www.steinel.net (800) 852-4343