Combustion air adjustments – CAMPO EQUIPMENT BLAZE 400G/MLPGFH315-400 Manuel d'utilisation
Page 15

HEAT EXCHANGER REASSEMBLY AFTER CLEANUP
1.) CLOSE EASY ACCESS PANEL LOCATED ON TOPSIDE OF HEAT EXCHANGER
2.) CLOSE TOP BOX EASY ACCESS PANEL
COMBUSTION AIR ADJUSTMENTS
AIR SETTINGS AND MANIFOLD PRESSURES & FIRING RATES FOR
MLPGFH315400
RECOMMENDED MANIFOLD PRESSURES FOR GAS OR PROPANE
Manifold pressure “W.C.
3.3
3.8
5.0
Input (BTU/h)
315,000
340,000
399,000
NATURAL GAS OPERATION
Head Setting
10.1
10.1
10.1
BECKETT BURNER
SPUD Style
Orifice
Orifice
Orifice
Combustion Air Adjustment
(shutter/band)
3/0
5.5/0
10/.5
PROPANE OPERATION
Head Setting
10.1
10.1
10.1
BECKETT BURNER
SPUD Style
Orifice
Orifice
Orifice
Combustion Air Adjustment
(shutter/band)
3/0
5/0
10/1
AIR SETTINGS AND MANIFOLD PRESSURES & FIRING RATES FOR
BLAZE 400G
BLAZE 400 G
SPECIFICATIONS
BLAZE 400G-RIELLO (NG/LP)
Input (BTU/h)
399,000
NG Set up (All
heaters come
factory set for
propane use)
Easy switch over Blue handle Ball Valve on Gas
manifold.
Closed position: Propane
Open position:
Natural Gas
CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)
6 Carson Court, Brampton, ON, CANADA, L6T 4P8
Tel: (905) 793-2525 | Fax: (905) 793-8768
P a g e