Chapter 1. Introduction
1–1 Applications
The Power+™ Control Units described in this publication
are used on Power Break® II insulated-case switches.
1–2 General
Power+ Control Units are the same size and have the same
connectors as the Power+ trip units and the RMS9D series
of MicroVersaTrip Plus™ and MicroVersaTrip PM™ trip
units.
Power+ Control Units may be tested with the Control Unit
installed in the switch, the rating plug installed in the
Control Unit, and the switch carrying current. The Test
Kit plugs into the test socket of the rating plug. The Test
Kit catalog number is TVRMS2 and its operation is
described in GEK–97367.
Power+ Control Units are removable from the switch. For
instructions on installing and removing the Control Unit,
see Chapter 4 of this guide or the appropriate switch
user’s guide.
CAUTION:
Removal of a Control Unit from its switch
must be performed with the switch in the
OPEN
or
TRIPPED
position. Draw-out switches should be racked
out first.
ATTENTION:
Pour retirer unité de contrôle,
l'interrupteur doit être en position ouverte ou
déclenchée. Les interrupteurs débrochables doivent ètre
en position débrochée.
CAUTION:
Do not attempt to operate the switch without
its assigned Control Unit. Installation of an incorrect
Control Unit may result in unsafe operation of the
switch.
ATTENTION:
Ne pas tenter d'opérer l'interrupteur sans
son unité de contrôle assignée. L'installation d'une unité
de contrôle incorrecte peut avoir comme conséquence
une opération non sécuritaire de l'interrupteur.
NOTE:
Control Units as received may have settings that
are undesirable for the specific application. Ensure that
settings are appropriately adjusted before energizing.
NOTE:
Unités de contrôle sont livrés avec des réglages
standards qui peuvent être inadéquates pour certaines
applications. Vérifier ces réglages avant de mettre le
disjoncteur sous tension.
1–3 Control Unit Functions
Power+ Control Units have specific standard and optional
functions. The standard function of the Control Unit is to
operate switch accessories.
The optional functions available are as follows:
• Protection
– Ground-fault protection, with or without I
2
T
• Status
– Ground-fault trip targets
– Health monitor
1–4 Control Unit Catalog Numbers
A simple catalog-numbering system defines all of the stan-
dard and optional Control Unit functions. A complete
catalog numbering key is found inside the front cover.
Each of the segments of the catalog number is described
below.
The first character indicates the switch type for which the
Control Unit is configured, as listed in Table 1.
Character Switch
Type
D
Power Break II
Table 1. Switch type referred to by the first character of the
Control Unit catalog number.
The second character of the catalog number indicates the
highest-rated current transformer (CT) sensor allowed for
that switch frame, as listed in Table 2.
Character Maximum
CT
2 2000
A
3 3000
A
4 4000
A
Table 2. Highest-rated CT allowed in the switch frame, given
by the second character of the Control Unit catalog number.
The third and fourth characters of the catalog number
indicate the CT that is actually installed in the switch, as
listed in Table 3.
Characters Installed
CT
08 800
A
16 1600
A
20 2000
A
25 2500
A
30 3000
A
40 4000
A
Table 3. Installed CT, as indicated by the third and fourth
characters of the Control Unit catalog number.
1