Set Receive to Transmit Delay
Request:
Paramètres
Length
Code/Data
Set Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Response:
Paramètres
Length
Code/Data
Set Receive to Transmit Delay
6 characters ASCII
UuuROK
Report Number of Floats
Request:
Paramètres
Length
Code/Data
Set Receive to Transmit Delay
4 characters ASCII
UuuF
Response:
Paramètres
Length
Code/Data
Set Receive to Transmit Delay
5 characters ASCII
UuuFn
n = number of measurement values
(0, 1 or 2)
Report Receive to Transmit Delay
Request:
Paramètres
Length
Code/Data
Report Receive to Transmit Delay
4 characters ASCII
UuuR
Response:
Paramètres
Length
Code/Data
Report Receive to Transmit Delay
7 characters ASCII
UuuRmmm
mmm = milliseconds (50 up to 250),
default = 127 ms
Codes de défaut
Error Code
Name
EE-Error
Error While Storing Data in EEPROM
FR-Error
Erorr in Frame (too short, too long, wrong data)
LV-Error
Value out of limits