VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) Modbus and Levelmaster protocol Manuel d'utilisation
Page 76

76
10 Annexe
VEGAPULS 62 • Protocole Modbus et Levelmaster
41362-FR-121120
Register Name
Register Number
Type
Note
Status
2000
DWord
See Register 100
PV
2002
DWord
Primary Variable in Byte Order ABCD (Big Endian)
SV
2004
DWord
Secondary Variable in Byte Order ABCD (Big Endian)
TV
2006
DWord
Third Variable in Byte Order ABCD (Big Endian)
QV
2008
DWord
Quarternary Variable in Byte Order ABCD (Big En-
dian)
Status
2100
DWord
See Register 100
PV
2102
DWord
Primary Variable in Byte-Reihenfolge DCBA (Little En-
dian)
SV
2104
DWord
Secondary Variable in Byte-Reihenfolge DCBA (Little
Endian)
TV
2106
DWord
Third Variable in Byte-Reihenfolge ABCD DCBA (Little
Endian)
QV
2108
DWord
Quarternary Variable in Byte-Reihenfolge DCBA (Little
Endian)
Status
2200
DWord
See Register 100
PV
2202
DWord
Primary Variable in Byte Order BACD (Middle Endian)
SV
2204
DWord
Secondary Variable in Byte Order BACD (Middle En-
dian)
TV
2206
DWord
Third Variable in Byte Order BACD (Middle Endian)
QV
2208
DWord
Quarternary Variable in Byte Order BACD (Middle En-
dian)
Unit Codes for Register 104, 108, 112, 116
Unit Code
Measurement Unit
32
Degree Celsius
33
Degree Fahrenheit
40
US Gallon
41
Liters
42
Imperial Gallons
43
Cubic Meters
44
Feet
45
Meters
46
Barrels
47
Inches
48
Centimeters
49
Millimeters
111
Cubic Yards
112
Cubic Feet