VEGA SOLITRAC 31 Foundation Fieldbus Manuel d'utilisation
Page 73

73
11 Annexe
SOLITRAC 31 • Foundation Fieldbus
41781-FR-130621
Hex
Quality
Sub-Status
Condition
0x4C
Uncertain
Initial Value
After startup of device or channel assignment
in AIFB was changed. The channel unit may be
unknown until next "Process Data Update"
On user error codes: 13
0x80
Good (NC)
Non-specific
No errors concerning to channel handling
On user error codes: 0, 33, 45, 71, 126, 127
Mapping of User Error Codes to FF Field Diagnostics
Priority
Description
User Error Codes
NE-107 Status
31
Hardware failure
40, 41
FAILURE
30
Memory failure
34, 35, 36, 37
FAILURE
29
Software failure
80
FAILURE
28
Paramererization corrupt
72
FAILURE
27
Undefined 27
-
-
26
Undefined 26
-
-
25
Paramererization error
16, 17, 25, 52, 53, 57, 66, 117,
120
FAILURE
24
Conflict in MGC
121, 122, 141
FAILURE
23
Communication error in MGC
8
FAILURE
22
MGC slave reports error
38
FAILURE
21
Undefined 21
-
-
20
Undefined 20
-
-
19
Undefined 19
-
-
18
Detector temperature critical
125
OUT_OF_SPEC
17
Error while auto-standardization
73
FAILURE
16
Excessive radiation
123, 124
FAILURE
15
Input out of bounds
13
OUT_OF_SPEC
14
Error while signal processing
68
FAILURE
13
Undefined 13
-
-
12
Undefined 12
-
-
11
Undefined 11
-
-
10
Undefined 10
-
-
9
Undefined 9
-
-
8
Undefined 8
-
-
7
AITB simulated
29
FUNCTION_CHECK
6
Undefined 6
-
-
5
Undefined 5
-
-
4
Undefined 4
-
-
3
Undefined 3
-
-