11 Annexe
VEGAPULS 62 version tube guide d'ondes • Foundation Fieldbus
36510-FR-121120
Transmitter Function Blocks
Resource Block (RB)
1
Transducer Block (TB)
1
Standard Block (AI)
3
Execution Time
30 mS
Advanced Function Blocks
Discret Input (DI)
Yes
PID Control
Yes
Output Splitter (OS)
Yes
Signal Characterizer (SC)
Yes
Integrator
Yes
Input Selector (IS)
Yes
Arithmetic (AR)
Yes
Diagnostics
Standard
Yes
Advanced
Yes
Performance
No
Function Blocks Instantiable
No
General Information
LAS (Link Active Scheduler)
Yes
Master Capable
Yes
Number of VCRs (Virtual Communication Re-
lationships)
24
Blocs de fonction
Transducer Block (TB)
Le Transducer Block "Analog Input (AI)" prend la valeur de mesure originaire (Secondary Value 2),
effectue le réglage mini.-/max. (Secondary Value 1), effectue une linéarisation (Primary Value) et
rend disponibles les valeurs à sa sortie pour d'autres blocs de fonction.
m(d)
%
Lin%
Primary
Value
Secondary
Value 2
Secondary
Value 1
TB
Sensor_Value
min/max
adjustment
Linearization
Fig. 28: Représentation schématique Transducer Block (TB)
Bloc de fonction Analog Input (AI)
Le bloc de fonction "Analog Input (AI)" prend la valeur de mesure originaire sélectionnée par un
Channel Number et le rend disponible à sa sotie pour d'autres blocs de fonction.