VEGA VEGAPULS 61 (≥ 2.0.0 - ≤ 3.8) Foundation Fieldbus Manuel d'utilisation
Page 65

Diagramme du réglage
La figure suivante montre la fonction du réglage.
Secondary_value_1
Calibration
Lowest Point
Calibration
Highest Point
Sensor_value
cal_level_lo
cal_level_hi
Calibration
Lowest Point
Calibration
Highest Point
Sensor reference plane
cal_level_lo [%]
cal_level_hi [%]
Fig. 41: Réglage VEGAPULS 61
Liste des paramètres
La liste suivante vous indique les paramètres les plus importants et leur signification :
l
primary_value
-
Process value after min/max-adjustment and linearization. Selected as input to AIFB by setting
'C
hannel' = 1. Unit derives from 'Primary_value_unit'
l
primary_value_unit
-
Selected unit code for "primary_value"
l
secondary_value_1
-
Value after min/max-adjustment (level + level offset). Selected as input to AIFB by setting
'C
hannel' = 2. Unit derives from 'Secondary_value_1_unit'
l
secondary_value_1_unit
-
Selected unit code for "secondary_value_1"
l
secondary_value_2
-
Sensor value + sensor offset. Selected as input to AIFB by setting 'Channel' = 3. Unit derives
from 'Secondary_value_2_unit'
VEGAPULS 61 • Foundation Fieldbus
65