Product overview and specifications – Dell Metered PDU LED Manuel d'utilisation
Page 2

2
Dell Metered Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Metered Rack PDU distributes power to the devices in the rack.
O
U T L E T S
— The Rack PDU has twenty (20) 5-15 R outlets.
P
O W E R
C O R D
— The Rack PDU has an IEC-320-C20 inlet and can be used with a detachable power cord (not provided).
G728N
Electrical
Input connection
IEC-320-C20
Acceptable input voltage
100–120 VAC
±
10%
Maximum input current (phase)
16 A
Input frequency
50/60 Hz
Input power
1.9 kVA UL and C-UL (derated), PSE
Output voltage
100–120 VAC (Line-to-Neutral)
Output connections
Twenty (20) 5-15 R
Maximum output current (outlet)
5-15 R: 12 A UL and C-UL (derated), PSE
Maximum output current (phase)
16 A UL and C-UL (derated), PSE
Physical
Dimensions
(H x W x D)
162.5 x 5.5 x 4.1 cm
(64.0 x 2.2 x 1.6 in)
Shipping dimensions
(H x W x D)
187.5 x 22.6 x 13.5 cm
(73.8 x 8.9 x 5.3 in)
Weight
4.1 kg (9.0 lb)
Shipping weight
5.9 kg (13.0 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing
5 to 95%, non-condensing