Dell Metered Rack Power Distribution Unit—Product Overview and Specifications
Product Overview and Specifications
The Dell Metered Rack PDU distributes power to the devices in the rack.
O
U T L E T S
— The Rack PDU has twenty (20) IEC-320-C13 outlets and six (6) IEC-320-C19 outlets.
P
O W E R
C O R D
— The Rack PDU has a NEMA
L6-30P
power cord.
G740N
Electrical
Input connection
NEMA L6-30P
Acceptable input voltage
200–240 VAC +6%, -10%
Maximum input current (phase)
24 A (derated)
Input frequency
50/60 Hz
Input power
5.8 kVA
Output voltage
200–240 VAC
(Line-to-Line or Line-to-Neutral)
Output connections
Twenty (20) IEC-320-C13; Six (6) IEC-320-C19
Maximum output current (outlet)
IEC-320-C13: 12 A; IEC-320-C19: 16 A
Maximum output current (phase)
24 A (derated)
Maximum output current (breaker)
16 A (derated)
Physical
Dimensions
(H x W x D)
162.5 x 5.5 x 4.6 cm
(64.0 x 2.2 x 1.7 in)
Depth at breakers: 9.4 cm (3.7 in)
Shipping dimensions
(H x W x D)
187.5 x 22.6 x 13.5 cm
(73.8 x 8.9 x 5.3 in)
Weight
6.0 kg (13.2 lb)
Shipping weight
7.8 kg (17.2 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
0 to 3048 m (0 to 10,000 ft)
0 to 15 240 m (0 to 50,000 ft)
Temperature
Operating
Storage
0 to 50°C (32 to 122°F)
–15 to 60°C (5 to 140°F)
Humidity
Operating
Storage
5 to 95%, non-condensing