Warning – Faber PELLICANO Cabinet Rangehood Manuel d'utilisation

Page 5

Advertising
background image

Version 07/11 - Page 5

For best results, use no more than three 90°

elbows. Make sure that there is a minimum

of 24" of straight duct between elbows if more

than one is used. Do not install two elbows

together. If you must elbow right away, do it

as far away from the hood's exhaust opening

as possible.

9 Feet Straight Duct

2 - 90˚ Elbows

Wall Cap

Total System

9.0 feet

10.0 feet

0.0 feet

19.0 feet

FIGURE 5

3.0 feet

5.0 feet

12.0 feet

0.0 feet

45˚ Elbow

90˚ Elbow

90˚ Flat Elbow

Wall Cap

FIGURE 4

CALCULATE THE DUCTRUN LENGTH

The ductrun should not exceed 35 equivalent feet if

ducted with the required minimum of 6" round duct.

Calculate the length of the ductwork by adding the

equivalent feet in FIGURE 4 for each piece of duct

in the system. An example is given in FIGURE 5.

PLAN THE DUCTWORK

The Pellicano rangehood is designed to offer wide

flexibility of installations. The rangehood can be

ducted vertically or horizontally through a 6" round

vent. The unit can also be installed in a recirculating

configuration. FIGURES 1 and 2 show vertical and

horizontal installations for this unit. FIGURE 3 shows

recirculating installation. For direct rear venting,

remove the 10 screws on the outside edge of the

exhaust plate and flip motor to the rear exit.

The Pellicano requires 6" round ductwork. To en-

sure that the blower performs to its highest possible

capacity, ductwork should be as short and straight

as possilbe.

WARNING! BEFORE MAKING ANY CUTS OR

HOLES FOR INSTALLATION, DETERMINE

WHICH VENTING METHOD WILL BE

USED AND CAREFULLY CALCULATE ALL

MEASUREMENTS.

FIGURE 1

FIGURE 2

ceiling

enclosed soffit

side view

rangehood

cooking surface

upper

cabinet

ceiling

open space

side view

rangehood

cooking surface

upper

cabinet

FIGURE 3A

FIGURE 3B

FIGURE 3C

WARNING

Because of the weight and size of the rangehood

canopy, two or more people are needed to move

and safely install the rangehood canopy.

Failure to properly lift rangehood could result in

damage to the product or personal injury.

PERSONAL INJURY HAZARD

!

RECIRCULATING INSTALLATIONS

For recirculating installations, Charcoal Filters are necessary. Remove all

grease filters and set aside. Attach one charcoal filter to each end of the

blower. Each charcoal filter attaches to the black grid on the side of the

blower. Rotate the filter clockwise to install and counterclockwise to remove

(FIGURE 3C). Replace all grease filters.

There are 2 ways to recirculate the Pellicano :

1)Use the Recirculation Kit

(sold seperately), refer to installation instructions

inside the Recirculation Kit.

2)Some ductwork must be installed to exhaust the rangehood back into the

kitchen, either at the top of the cabinet (FIGURE 3A) or at the face or side

of the soffit (FIGURE 3B). Install at least 15" of metal ducting (fig. 3A and

3B) at the air exit. Run the duct vertically and secure it at the opening cut

out at the top or side of the cabinet or soffit. Installation of a metal grill is

recommended. This duct work must not terminate into a dead air space.