SYMPTOM

Burner fails to light

Pilot lights but goes out when

automatic control valve button

is released

Burn rate is low

POSSIBLE CAUSE

1. Gas supply valve closed

2. Excess-flow check valve

closed (propane/LP units

only)

3. Blockage in burner orifice

4. Piezo ignition system not

sparking

1. Not enough warm-up time

2. Low gas pressure

3. Thermocouple loose or needs

to be replaced

4. Automatic control valve needs

to be replaced

1. Main burner valve not fully

open

2. Plugged gas orifices

3. Low gas pressure

4. Low fuel supply

REMEDY

1. Open gas supply valve slowly

2. Close propane supply valve

on propane tank and reopen

slowly

3. Replace burner orifice

4. Assure ignitor electrode gap is

5.0 mm (.195 in). Check wire

lead for damage Replace piezo

ignitor and/or ignitor electrode

as necessary. Do not bend elec-

trode, this may cause breakage

1. Relight, hold automatic control

valve button in 45 seconds

2. Check for proper gas supply

3. Tighten connection or replace

thermocouple

4. Replace automatic control

valve

1. Fully open main burner valve

by pushing in control knob

and turning counterclockwise

towards HIGH position until

it stops

2. Replace gas orifice

3. Check gas supply; check

regulator output

4. Consult gas supplier to deter-

mine adequate supply. If using

propane/LP gas, the tank could

be empty

TROUBLESHOOTING

WARNING: Never attempt to service heater while it is connected

to propane supply, operating or hot. Severe burns can occur.